| CVE |
Vendors |
Products |
Updated |
CVSS v3.1 |
| Sensitive endpoints in Fresenius Kabi Agilia Link+ v3.0 and prior can be accessed without any authentication information such as the session cookie. An attacker can send requests to sensitive endpoints as an unauthenticated user to perform critical actions or modify critical configuration parameters. |
| Fresenius Kabi Vigilant Software Suite (Mastermed Dashboard) version 2.0.1.3 allows user input to be validated on the client side without authentication by the server. The server should not rely on the correctness of the data because users might not support or block JavaScript or intentionally bypass the client-side checks. An attacker with knowledge of the service user could circumvent the client-side control and login with service privileges. |
| MMP: All versions prior to v1.0.3, PTP C-series: Device versions prior to v2.8.6.1, and PTMP C-series and A5x: Device versions prior to v2.5.4.1 does not perform proper authorization and authentication checks on multiple API routes. An attacker may gain access to these API routes and achieve remote code execution, create a denial-of-service condition, and obtain sensitive information. |
| Automation Direct CLICK PLC CPU Modules: C0-1x CPUs with firmware prior to v3.00 does not protect against additional software programming connections. An attacker can connect to the PLC while an existing connection is already active. |
| All programming connections receive the same unlocked privileges, which can result in a privilege escalation. During the time Automation Direct CLICK PLC CPU Modules: C0-1x CPUs with firmware prior to v3.00 is unlocked by an authorized user, an attacker can connect to the PLC and read the project without authorization. |
| After Automation Direct CLICK PLC CPU Modules: C0-1x CPUs with firmware prior to v3.00 is unlocked by an authorized user, the unlocked state does not timeout. If the programming software is interrupted, the PLC remains unlocked. All subsequent programming connections are allowed without authorization. The PLC is only relocked by a power cycle, or when the programming software disconnects correctly. |
| Navigating to a specific URL with a patient ID number will result in the server generating a PDF of a lab report without authentication and rate limiting. |
| Improper access controls in the B. Braun Melsungen AG SpaceCom Version L81/U61 and earlier, and the Data module compactplus Versions A10 and A11 enables attackers to extract and tamper with the devices network configuration. |
| The setup program for the affected product configures its files and folders with full access, which may allow unauthorized users permission to replace original binaries and achieve privilege escalation. |
| mySCADA myPRO versions prior to 8.20.0 does not restrict unauthorized read access to sensitive system information. |
| The Weintek cMT product line is vulnerable to various improper access controls, which may allow an unauthenticated attacker to remotely access and download sensitive information and perform administrative actions on behalf of a legitimate administrator. |
| Successful exploitation of this vulnerability on Claroty Secure Remote Access (SRA) Site versions 3.0 through 3.2 allows an attacker with local command line interface access to gain the secret key, subsequently allowing them to generate valid session tokens for the web user interface (UI). With access to the web UI an attacker can access assets managed by the SRA installation and could compromise the installation. |
| Matrikon, a subsidary of Honeywell Matrikon OPC Server (all versions) is vulnerable to a condition where a low privileged user allowed to connect to the OPC server to use the functions of the IPersisFile to execute operating system processes with system-level privileges. |
| A vulnerability classified as problematic has been found in GE Voluson S8. Affected is the file /uscgi-bin/users.cgi of the Service Browser. The manipulation leads to improper authentication and elevated access possibilities. It is possible to launch the attack on the local host. |
| LRM does not implement authentication or authorization by default. A malicious actor can inject, replay, modify, and/or intercept sensitive data. |
| An attacker with weak credentials could access the TCP port via an open FTP port, allowing an attacker to read sensitive files and write to remotely executable directories. |
| An authenticated user with admin privileges may be able to terminate any process on the system running Elcomplus SmartICS v2.3.4.0. |
| By using a specific credential string, an attacker with network access to the device’s web interface could circumvent the authentication scheme and perform administrative operations. |
| SMS-based GPS commands can be executed by MiCODUS MV720 GPS tracker without authentication. |
| Softing Secure Integration Server, edgeConnector, and edgeAggregator software ships with the default administrator credentials as `admin` and password as `admin`. This allows Softing to log in to the server directly to perform administrative functions. Upon installation or upon first login, the application does not ask the user to change the `admin` password. There is no warning or prompt to ask the user to change the default password, and to change the password, many steps are required. |